Metering. Leader...Since 1904 TESCO - The Eastern Specialty Company
www.tesco-advent.com
Advent Design Corporation

TESCO Service Ground Test Set
Catalog No. 900

TESCO's Service Ground Test Set has been designed to check the condition of the
ground connection on a secondary service. If for any reason the ground connection has
a resistance, this can be immediately detected by the Test Set.

The Service Ground Test Set consists of a voltmeter which can be shunted by a resistance of 60 ohms. The voltmeter is of the suppressed zero type with a double range, from 65 to 130 or from 130 to 260, and can be used for checking service voltage independently of the ground test.

When making the ground test, connect one lead to a live 120 V leg of the service and the other lead to the ground connection. Depress the range button marked "130 V." The voltmeter will indicate the prevailing voltage. Then depress the button marked "Ground Test." Two amperes will now flow through the shunt resistor and the ground return. If the resistance of the ground is zero, then there should be no change in the reading of the voltmeter.

But if the ground connection has measurable resistance, then part of the IR drop will be across the ground, leaving less across the shunt resistor, and the reading of the voltmeter will drop.

The suppressed zero magnifies the visible effect of the voltage drop and also facilitates reading of the actual voltage on a small meter of this type. Scale divisions are in increments of two volts in terms of the low range, four volts on the high range.

To assist in making a rapid check of the condition of the ground, the voltmeter scale is divided into colored sectors as follows:

- Red - 65 to 86 Volts
- Yellow - 86 to 106 Volts
- Green - 106 to 130 Volts

The 86 and 106 volt points correspond, respectively, to ground resistance of 24 and 8 ohms.

In addition to checking service grounds, the Service Ground Test Set can be used to check the condition of potential transformers on transformer rated metering installations. The current drain at 120 volts is 2 amperes, which will place a burden of 240 voltamperes on the secondary of the potential transformer. Any excessive deflection of the voltmeter will then indicate a condition requiring further investigation.

Specifications
  • Dimensions: 4-1/8" x 2-5/8" x 6-1/2" (W x D x H)
  • Weight: 1.375 lbs.
Accessories
  • Carrying Case, Catalog No. 901
Service Ground Test Set
Service Ground Test Set
Catalog No. 900
Purchase Tesco Equipment
Call now. Contact TESCO sales to order direct at:
1-800-762-8211
To order spare or replacement parts for this item please contact your TESCO representative directly or call the number above.
Home I About Us I TESCO Equipment & Services I Metering Software I Meter Conferences & Schools I Meeting Center I Contact Us