Knopp logo

Voltage Transformer Testing System
KVTS

The Knopp Voltage Transformer Testing System is designed to measure the accuracy of instrument transformers having 120 volt secondaries and up to 14,400 volt primaries (special order for up to 36,000 volt primaries is available). The system includes a control console which contains the control circuitry, ANSI standard burdens, and the Knopp Automatic Transformer Comparator. The Knopp precision and loading transformer set is also included (as pictured) and is connected to the console via a special cable.

Some of the features of the KVTS include:

  • AUTOMATIC and AUTORANGING Voltage Transformer Comparator (Type KATC-V) provides minimal measurement time (typically a few seconds after adjustment of test voltage).
  • DIGITAL DISPLAY of test voltage, ratio error (in Percent or Ratio Correction Factor), phase angle error (in Minutes or Milliradians) is provided by the Comparator (KATC-V).
  • ACCURACY CLASS for which the transformer-under-test qualifies is calculated and digitally displayed by the Comparator (KATC-V).
  • SELF CHECK feature allows the system accuracy to be easily verified without the use of an external standard.
  • PROTECTIVE CIRCUITRY senses unusual error conditions, such as wrong ratio or wrong polarity, and then automatically removes power from the KVTS, precision transformer, and the transformer-under-test.
  • ZERO START feature requires that both coarse and fine controls of test voltage be at zero before power can be applied to the loading circuitry.
  • COMPUTER or PRINTER communication is available through an optional RS-232 port.
  • VOLTAGE TRANSFORMER TEST SET including a high precision multi-range voltage transformer and a heavy duty supply transformer plus the T-bar assembly and wheeled base.
  • INTERCONNECTING CABLES between the control console and the transformer test set.
  • All ANSI BURDENS including W, X, M, Y, Z and ZZ.
Specifications
  • Dimensions: 61.5" (156.5 cm) high, 24" (61 cm) wide, 37" (94 cm) deep console and 36" (91.5 cm) high, 25" (63.5 cm) wide, 20" (50.8 cm) deep voltage test set.
  • Weight: 350 lbs. (159.7 kg) console, and 300 lbs. transformer test set.
  • System Accuracy: within ±0.025% on ratio and ±2 minutes on phase angle at 1.2, or less, accuracy class.
  • Primary Ranges:120, 240, 288, 300, 480, 600, 2400, 4200, 4800, 7200, 8400, 12,000, 14,400 volts. Consult factory on other ranges.
  • ANSI Burdens: ANSI W, X, M, Y, Z, and ZZ; switch selectable. Provisions are made for use of an external burden.
  • Input Power: 120 VAC, 60 Hz; single phase; 10 amperes maximum.
  • Connecting Cable: 15 feet long (between transformer set and console).
Equipment Documentation

KVTS
Voltage Transformer Testing System
KVTS
Purchase Knopp Equipment
Call now. Contact TESCO sales to order direct at:
215-785-2338

Or contact Knopp sales to order at:
510-653-1661
Field repair and calibration are also available if you are not ready to replace your exisiting transformer test system. Contact us for more information.